Skip to main content
Version: v2 (latest)

Communication and Integration

RE-PLUG provides several communication interfaces, used to acquire data from the meter, send data to the cloud, and integrate with local devices and supervisory systems.

InterfacePurpose
PLC Narrow Band (Chain 2)Data acquisition from the 2G electronic meter
2.4 GHz Wi-FiConnection to the local network, the cloud platform, and Modbus TCP devices
Bluetooth® 4.2Commissioning and diagnostics with the e-snapp App (GATT Server; BLUFI on older units)

Communication with the 2G Meter (Chain 2)​

The device communicates with the second-generation electronic meter via power line communication (PLC Narrow Band), according to the Chain 2 standard.

ParameterValue
ModemC-Band
ModulationB-PSK
StandardChain2Full
ApplicationDLMS/COSEM IEC 62056-5-3
Data ModelCOSEM IEC 62056-6-1 / 6-2
ComplianceTS CEI 13-82:2020-04
TS CEI 13-83:2020-04
TS CEI 13-84:2020-04

Wi-Fi and Bluetooth​

InterfaceCharacteristics
Wi-FiIEEE 802.11 b/g/n, 2.4 GHz band, up to 150 Mbps
BluetoothBluetooth v4.2, BLUFI + GATT Server mode, integrated antenna

The configuration procedures are described on the Commissioning page.

IoT Protocols​

The device natively supports the following protocols:

  • MQTT
  • WebSocket
  • REST API
  • JCD Protocol
  • MODBUS TCP

Modbus TCP​

Modbus TCP Server​

  • Modbus TCP server over the Wi-Fi interface
  • Electrical data maps exposed via Modbus
  • Local supervision over TCP/IP
  • Interoperability with SCADA/BMS/EMS platforms

Modbus TCP Master​

  • Modbus TCP Master mode
  • TCP client communication over Wi-Fi
  • Supervision of field devices
  • Remote control of energy devices
  • Integration with third-party equipment

The device supports communication with:

  • Energy storage systems
  • Photovoltaic inverters
  • Generation systems
  • Heat pumps
  • EV chargers
  • Modbus TCP devices

Cloud & Edge Architecture​

  • Peer-to-Peer communication
  • Local and cloud supervision
  • Real-time telemetry
  • Remote provisioning
  • Remote firmware update (FOTA – Firmware Over The Air)
  • Remote certificate update

Cybersecurity​

RE-PLUG complies with the cybersecurity requirements of the EN 18031-1 standard and the RED Directive (Radio Equipment Directive).

Security features include:

  • TLS communications
  • Client/Server certificates
  • MQTT security
  • Authenticated provisioning
  • Secure cloud endpoint management