Skip to main content
Version: v2 (latest)

Specifications

Electrical Characteristics

General Specifications
General SpecificationsParameterDescription
Network Type1P + N
Sampling Rate6.99 kSPS
MeasurementsActive Power (W), Reactive Power (VAR), Apparent Power (VA), Active Energy (kWh), Reactive Energy (kVARh), Apparent Energy (kVAh), IRMS, VRMS
Power Factor
Compliant with EN 50470-1, EN 50470-3, IEC 62053-21, IEC 62053-22, and IEC 62053-23 standards
Display0.96″ OLED, 128 × 64 pixels, monochrome
Real-Time ClockNTP synchronized. Time accuracy: ±1 ppm @ 25°C
Data and Event LoggingOnline and onboard real-time data and event logging
Power Inputs
Power InputsParameterDescription
Number of Inputs2 inputs: Phase and Neutral (shared with Voltage Inputs)
Voltage Range90–300 VAC
Frequency Range50–60 Hz
Maximum Current0.15 A
Overcurrent ProtectionInternal Fuse (1 A, 350 VAC)
Overvoltage ProtectionInternal MOV + GDT
Voltage Inputs
Voltage InputsParameterDescription
Number of Inputs2 inputs: Phase and Neutral
Maximum Input Voltage300 V L-N
Measurement Category300 V CAT III
Overcurrent ProtectionInternal Fuse (1 A, 350 VAC)
Overvoltage ProtectionInternal MOV + GDT
Current Inputs
Current InputsParameterDescription
Number of Inputs1 input
Input TypeCurrent Transformers (CTs)
Maximum Input Current0.1 A
Current Transformer75 A : 0.1 A, Ø 10 mm
Accuracy
AccuracyParameterDescription
Voltage0.2%
Power Factor±0.001
Active/Apparent PowerClass 0.2
Reactive PowerClass 0.2
Frequency0.05% from 45 to 65 Hz
Active EnergyClass 0.2
Reactive EnergyClass 0.2

Mechanical Characteristics

Mechanical
MechanicalParameterDescription
Dimensions (L × W × H)35 mm × 86 mm × 59 mm
DIN Rail Size2M
Weight0.110 kg
Degree of ProtectionIP40 front panel, compliant with IEC 60529
IP20 enclosure, compliant with IEC 60529

Environmental Characteristics

Environment
EnvironmentParameterDescription
Operating Temperature-40 °C to +65 °C
Humidity5% to 95% RH at 50 °C (non-condensing)
Pollution Degree2

Safety and Standards

Safety
SafetyParameterDescription
General ComplianceCE compliant according to IEC 61010-1 (double insulation)
Pollution Degree2
Overvoltage CategoryOVC III (2000 m)
Operating AltitudeUp to 2000 m

Communication

Communication
CommunicationParameterDescription
Wi-Fi2.4 GHz Wi-Fi (802.11 b/g/n)
BluetoothBluetooth® 5 (LE)
ModbusModbus TCP/IP
MQTTMQTT Client
MQTTs Client (TLS-encrypted)
RS485 Insulation5.7 kV reinforced insulation

Cybersecurity

Cybersecurity
CybersecurityParameterDescription
Data EncryptionMQTT data transfer over TLS
Flash EncryptionAES-XTS-based flash encryption
User AccessStrong password enforcement
Event LoggingSecurity event logging via Syslog
Secure BootRSA-based secure boot
ServicesUnused services and ports can be disabled
Wi-FiProtected Management Frames (PMF) support