General Specifications

ParameterDescription
Network Type1P + N · 2P + N · 3P + N WYE (Y)
Sampling Rate8 kSPS
MeasurementsTotal and fundamental Active Power (W), Reactive (VAR), Apparent (VA); Active (kWh), Reactive (kVARh), Apparent (kVAh) energy; total and fundamental IRMS and VRMS; total harmonic distortion (THD); power factor. Active energy: IEC 62053-21/22, EN 50470-3, OIML R46, ANSI C12.20. Reactive energy: IEC 62053-23/24.
Display2.0" active matrix TFT, 320 × 240 pixels, 65K colors
Real Time ClockNTP synchronized, accuracy ±1 ppm @ 25 °C
Data and Event LoggingOnline and onboard real-time data and event logging

Power Inputs

ParameterDescription
Number of Inputs2 inputs: Phase and Neutral
Voltage Range90–300 VAC
Frequency Range50–60 Hz
Max. Current0.15 A
Overcurrent ProtectionInternal fuse (1 A, 350 V AC)
Overvoltage ProtectionInternal MOV + GDT

Voltage Inputs

ParameterDescription
Number of Inputs4 inputs: 3 Phases and Neutral
Max. Voltage Input300 V L-N
Measurement Category300 V CAT III
Overcurrent ProtectionInternal fuse (1 A, 350 V AC)
Overvoltage ProtectionInternal MOV + GDT

Current Inputs

ParameterDescription
Number of Inputs4 inputs: 3 Phases and Neutral
Input TypeCurrent Transformers (CT) · Rogowski Coils
Compatible CTs75A:0.1A Ø10mm · 150A:0.1A Ø16mm · 300A:0.1A Ø24mm · 600A:0.1A Ø36mm · 1200A:0.1A Ø90mm · 2500A:0.1A Ø120mm
Compatible Rogowski1000A Ø120mm · 2000A Ø190mm · 3000A Ø300mm

Accuracy

ParameterDescription
Voltage0.2 %
Power Factor± 0.001
Active / Apparent PowerClass 0.2
Reactive PowerClass 0.2
Frequency0.05 % from 45 to 65 Hz
Active EnergyClass 0.2
Reactive EnergyClass 0.2

Power Quality Analysis

ParameterDescription
ClassIEC 61000-4-30 Class S
MeasurementVRMS½ / IRMS½ (refreshed each half cycle) · 10/12 cycle RMS · voltage and current unbalance · zero crossing · phase angle
Anomalies DetectionDip and Swell monitor · event waveform capture · zero-crossing timeout
Line FrequencyOne per phase
Harmonics AnalysisIndividual harmonic magnitudes on voltage and current, up to the 63rd harmonic
Harmonics DistortionVoltage (VTHD) · Current (ITHD)
WaveformCapture on all voltage and current inputs (including Neutral)

Mechanical

ParameterDescription
Dimensions (L×W×H)70 mm × 91 mm × 59 mm
DIN-Rail Size4M
Weight0.210 kg
Degree of ProtectionIP40 front panel · IP20 body (conforming to IEC 60529)

Safety

ParameterDescription
GeneralCE as per IEC 61010-1 (double insulation)
Pollution Degree2
Overvoltage CategoryOVC III (5000 m)
Operating AltitudeUp to 5000 m
RS485 Insulation5.7 kV reinforced insulation

Environment

ParameterDescription
Operating Temperature-40 °C to +65 °C
Humidity Rating5–95 % RH at 50 °C (non-condensing)
Pollution Degree2

Cybersecurity

ParameterDescription
Data EncryptionMQTT data transfer over TLS
Flash EncryptionAES-XTS-based flash encryption
User AccessStrong password enforcement
Event LoggingSecurity events logging via Syslog
Secure BootRSA-based secure boot
ServicesUnused services and ports can be disabled
Wi-FiProtected Management Frames (PMF) support
ConformityCompliant with EN 18031-1 and Delegated Regulation (EU) 2022/30 (RED)

Communication & current inputs by variant

ModelWi-FiBluetoothMQTTModbus TCP/IPModbus RTULoRaWANEthernetCT Split CoreRogowskiZigBee
RE-431-D
RE-431-D-RS485
RE-431-D-LW
RE-431-D-ETH
RE-431-D-ROG