Installation
The device can be installed inside an electrical panel on a DIN rail. Follow the steps below to install the device.
The installation, operation, and maintenance of electrical equipment must be carried out exclusively by qualified personnel. Renua SocietΓ Benefit S.r.l. assumes no responsibility for any consequences arising from the use of this material. Qualified personnel are individuals who possess adequate skills and knowledge regarding the construction, installation, and operation of electrical equipment and who have received appropriate safety training to recognize and avoid inherent hazards. REFER TO THE Safety Information SECTION.
Mountingβ
The figures below illustrate how to mount and remove the device from a DIN rail:
Figure 2 β DIN Rail Mounting and Removal
Wiringβ
All operations described in this section must be performed exclusively by qualified personnel in accordance with applicable technical and safety regulations.
Installation of the device involves interaction with mains voltages up to 400 V. Failure to comply with safety requirements may result in serious electric shock hazards, equipment damage, and risks to personnel.
The analyzer must be installed downstream of a suitably rated circuit breaker or disconnect switch, clearly identified and located near the device so that it can be easily accessed for isolation purposes.
Before starting any installation or wiring activity, ensure that the circuit breaker or disconnect switch is in the OFF position and verify the absence of voltage using a properly calibrated testing device.
π§° Required Materialsβ
- RE-211 β Three-phase Energy Meter (DIN rail version)
- DIN rail (35 mm standard)
- Electrical cables (cross-section suitable for the load and compliant with applicable standards)
- Screwdrivers, wire strippers, multimeter
- Cable terminals (optional but recommended)
- Circuit breaker (recommended between the supply line and the meter)
- This technical manual (essential for the correct wiring diagram)
π οΈ Installation and Wiring Procedure (DIN Rail Version)
- Disconnect power from the system and verify the absence of voltage on the conductors using an appropriate measuring instrument (e.g., a properly calibrated and functioning multimeter).
- Install the RE-211-D device on a standard 35 mm DIN rail as shown in Figure 2, ensuring that it is securely attached.
- Connect the current input to the current transformer (CT) according to the wiring diagram, ensuring the correct correspondence between phases and inputs:
L β CT
This operation must be performed before mounting the CTs on the power conductors to ensure correct phase association.
- Mount the current transformer (CT) on the phase conductor (L).
It is essential that the directional arrow marked on each CT is oriented from the measurement point (meter or source β identified as "K") toward the load (electrical panel β identified as "L"), as illustrated in the figure below.
Incorrect CT installation may compromise the accuracy of current measurements and energy flow direction detection.
Figure 3 β Current Transformer (CT) Installation
- Connect the phase voltage inputs [VOLTAGE INPUTS] according to the supplied wiring diagram. The use of a dedicated circuit breaker (2-pole, 6 A or 10 A rating, minimum breaking capacity 4.5 kA) is strongly recommended for single-phase installations. This solution improves safety, efficiency, and regulatory compliance for the following reasons:
- Provides adequate protection against overloads and short circuits, reducing the risk of permanent damage.
- Allows functional isolation of the equipment, facilitating safe maintenance, inspection, or replacement without affecting the power continuity of the installation.
- Meets the requirements of applicable technical standards (e.g., IEC/CEI 64-8) and aligns with industry best practices.
- Simplifies wiring organization, making fault identification and troubleshooting easier.
Figure 4 β RE-211-D Power Supply Connection
- Connect the [POWER INPUT] terminals to provide power to the device.
Whenever possible, it is recommended to connect the power inputs to an auxiliary or preferred power line to ensure continuous operation of the analyzer even in the event of faults or interruptions on the monitored electrical lines.
Figure 5 β RE-211 Energy Meter General Wiring
Wi-Fi Network Connectionβ
Wi-Fi configuration and adding the analyzer to your account are performed with the e-snapp App, which communicates with the device via Bluetooth.
To ensure a stable and reliable connection, the Wi-Fi signal must be adequate and the network must have Internet access.
The screenshots in this manual show the App in Italian; the steps are the same in every language.
Before You Startβ
- Analyzer installed and powered, as described in the previous sections.
- e-snapp App installed on the smartphone, signed in with your account.
- Bluetooth enabled on the smartphone; camera access granted to the App, to scan the QR code.
- 2.4 GHz Wi-Fi network with Internet access, and its password.
The "Add device" button is available when the active location (home) does not yet contain any device, and only to the owner or an administrator of the location.
1. Add the Deviceβ
On the App home screen, tap "Add device", then choose "In the electrical panel" (DIN Rail Β· RE-2XX / RE-4XX Series).


2. Prepare the Deviceβ
Check that the analyzer is correctly mounted on the DIN rail and powered, and that the status LED is blinking. Keep the smartphone close to the panel during pairing, then tap "Device ready".

3. Pair the Deviceβ
At first power-on (or after resetting the Wi-Fi settings), the analyzer shows a QR code on its display: frame it with the camera inside the App viewfinder. The first time, the App asks for permission to access the camera.
Alternatively, tap "Enter the code manually", type the 8-character alphanumeric code shown on the device display and tap "Connect Device".


4. Bluetooth Connectionβ
The App searches for the analyzer via Bluetooth and establishes communication with the device. When finished, the message "Connected successfully" is shown.


5. Wi-Fi Connectionβ
- Select the Wi-Fi network from the list of detected networks (only 2.4 GHz networks are supported).
- Enter the network password and tap "Connect device".
- Wait for the connection to complete.
The password is not stored on e-snapp servers.


6. Name the Deviceβ
Enter a name for the analyzer and tap "Finish setup". When finished, the message "Device configured successfully" is shown: tap "Continue" to return to the App.


For stable operation, the Wi-Fi signal level should be higher than -70 dBm.
Data collected during measurements is sent to the cloud and can be accessed through the e-snapp App and the Web Dashboard.
Functionsβ
Analyzer Featuresβ
The analyzer measures line current and voltage and displays RMS values in real time. It also calculates power factor, active power, reactive power, and apparent power.
Energy Readingsβ
The analyzer calculates and stores total and partial energy values for active, reactive, and apparent energy.
Energy values can be viewed on the display. The energy unit automatically changes from kWh to MWh (and from kVAh to MVARh) according to the measured value.
Analyzer Operationβ
Overviewβ
The analyzer features a front panel that includes a status LED indicator, a color graphic display, and a set of contextual function buttons.
These elements allow the operator to intuitively access operational information and to view, configure, and modify operating parameters according to application requirements.
The navigation menu allows users to view, configure, and reset parameters.
Display Screen Overviewβ

| A | Wi-Fi Signal Strength and SSID |
| B | Time β Local Format [HH:MM:SS] |
| C | Screen Content |
| D | Wi-Fi Interface IP Address |
| E | Status Notifications |
Status Informationβ
The status LED on the front panel indicates the current operating status of the analyzer.
The icons in the following table indicate the LED status:
| Analyzer Powered Off | Startup Phase | Not Connected | Analyzer Connected |
Reset and Factory Settings Restorationβ
To restore the factory Wi-Fi or password settings, proceed as follows:
- Disconnect power from the device and then restore power. During startup, simultaneously press and hold the UP and DOWN buttons until a confirmation message appears on the display indicating that the Wi-Fi configuration and password have been restored to factory defaults.
Figure 17 β Wi-Fi and Password Factory Reset
Maintenance and Troubleshootingβ
Overviewβ
The analyzer contains no user-serviceable components. For maintenance or repair operations, please contact technical support at support@renua.it.
- Do not open the analyzer enclosure.
- Do not attempt to repair analyzer components.
Do not open the analyzer. Opening the analyzer voids the warranty.
Diagnostic Codesβ
If anomalies are indicated by the status LED and/or error icons on the display, the system will automatically show a diagnostic code corresponding to the detected condition. If the issue persists after applying the recommended corrective actions, contact technical support.
| Diagnostic Code | RE-211 | Description | Possible Solution |
|---|---|---|---|
| - | β | Status LED appears to be off | Restart the analyzer by powering it off and on again |
| - | β | Buttons do not respond | Restart the analyzer by powering it off and on again |
Maintenance and Troubleshootingβ
| Diagnostic Code | RE-211 | Description | Possible Solution |
|---|---|---|---|
| 001 | β | The analyzer stops due to an internal error | Restart the analyzer by powering it off and on again |
| 002 | β | The analyzer is operating. Frequency settings do not match measured frequency | Correct the frequency settings according to the nominal network frequency |
| 003 | β | The analyzer is operating. Wiring settings do not match wiring inputs | Correct the wiring settings according to the actual wiring inputs |
| 004 | β | The analyzer is operating. Phase sequence is reversed | Check cable connections or correct the wiring settings |
| 005 | β | The analyzer is operating. Date and time have been reset due to a power interruption | Restart the analyzer by powering it off and on again. Verify the device's Internet connection |